158 Rockwell Automation Publication 7000-UM202H-EN-P - November 2023
Chapter 3 Control Component Definition and Maintenance
Non-Isolated Process Outputs
The drive supplies four non-isolated -10/0/+10 V outputs for your use. These
outputs can drive loads with impedances as low as 600 Ω. These outputs are
referenced to the Drive AGND; isolate them if you require them to drive
outside the frame enclosure.
Figure 135 - Non-isolated configurable ACB analog outputs
Auxiliary +24V Power Supply
The DC/DC converter has a built-in isolated 24V power supply (Connector P3).
Use this supply for any equipment requiring up to 24 W at 24V. You can also
use the supply to power any custom drive options, such as isolation modules
for additional process control outputs. The health of this power supply is
monitored in the drive.
DSP
FPGA
A/D
IFM Pin#
27, 31, 35, 39
Analog Input
25, 29, 33, 37
28, 32, 36, 40
PIN NO. DESCRIPTION
1 ISOLATOR (+24V, 1 A)
2 ISOL_COMM (com4)
3EARTH