Dips and Interrupts per EN 61000-4-11
Electrical Fast Transients (EFT)
per EN 61000-4-4
1 kV signal, 2 kV AC power
Electrical Surge Immunity
per EN 61000-4-5
AC power: 2 kV common mode, 1 kV differential mode
Electrostatic Discharge (ESD) PXC-16 and PXC-24: per EN 61000-4-2, 6 kV contact, 8 kV air discharge
PXC-36: per EN 61000-4-2, 4 kV contact, 8 kV air discharge
RF Conducted Immunity per EN 61000-4-6 @ 10V
RF Radiated Immunity per EN 61000-4-3 @ 10V/m
Sensor Limits
Voltage Input 0 to 11 Vdc -1.0 Vdc -0.5 Vdc +12.0 Vdc +11.5 Vdc
Current Input 4 to 20 mA 3.68 mA 3.92 mA 21.5 mA 21.0 mA
10KΩ Thermistor
-58°F to +302°F
(-50°C to +150°C)
-65°F -60°F +320°F +311°F
100KΩ Thermistor
-58°F to +302°F
(-50°C to +150°C)
-65°F -60°F +320°F +311°F
Pt 1KΩ RTD
(TC 375)
-40°F to +248°F
(-40°C to +120°C)
-55°F -60°F +266°F +257°F
Pt 1KΩ RTD
(TC 385)
-58°F to +752°F
(-50°C to +400°C)
-75°F -57°F +770°F +761°F
Ni 1KΩ RTD
-58°F to +302°F
(-50°C to +150°C)
-65°F -60°F +320°F +311°F
1000 Ω Nickel DIN
Standard
-58°F to +302°F
(-50°C to +150°C)
-65°F -60°F +320°F +311°F
JCI Nickel 1000K
-40°F to 180°F
(-40°C to 82°C)
-55°F -50°F +240°F +220°F
10K Termistor Type 3
-58°F to +302°F
(-50°C to +150°C)
-65°F -60°F +320°F +311°F
Communication Connections
The PXC Compact Series provides the following communication connections:
● HMI and Tool ports
● 10B/100B Ethernet port
● RS-485 port
● USB Host Port
● TX-I/O Island Bus (PXC-36 only)
PXC Compact hardware that contains both a 10B/100B Ethernet port and an RS-485
port can be configured through the HMI to reside on any of the following:
● BACnet/IP or Ethernet TCP/IP (P2) ALN
● RS-485 P2 or BACnet MS/TP ALN