Hardware Features
PXC Compact on P1
58
| 100
Siemens Industry, Inc.
145-172
Building Technologies
Restricted
2018-09-25
02028C ASSIGN DAY OF MONTH TO FIELD PANEL DAY OF MONTH VALID
VALUES 1 TO 31
02030$ARG3 = $VDAYM
02038C ASSIGN HOURS TO FIELD PANEL HOURS VALID VALUES 0 TO 23
02040$ARG4 = $VHOUR
02048C ASSIGN MINUTES TO FIELD PANEL MINUTES VALID VALUES 0 TO
59
02050$ARG5 = $VMIN
02058C ASSIGN VTIME ON IN THIS PXC COMPACT ON P1
02060ON($ARG6)
02070RETURN
. . .
31998C RETURN CONTROL TO MAINLINE PROGRAM
32000GOTO 10
Synchronizing System Time in a PXC Compact on P1
System time in the PXC Compact on P1 can be synchronized daily by the host field
panel.
The resident P1 points SYNC HOUR (value of 0 to 23) and SYNC NOW (value of
ON or OFF) can be commanded by the host field panel over the FLN.
For example, if the SYNC HOUR point is commanded to 2.0, when the SYNC NOW
point is commanded to ON, the time at the PXC Compact on P1 will be set to 2:00 a.m.
Note that the SYNC NOW point is automatically reset to OFF by the PXC Compact on
P1 once it syncs its time.
Add Mainline PPCL to Call a Subroutine for each PXC Compact on P1
Hosted to Synchronize Time Once Daily
. . .
00992C
00994C MANAGE SYNCHRONIZING TIME ONCE DAILY IN ALL PXC COMPACT
ON P1 HOSTED BY THIS FIELD PANEL
00996C LOCKOUT $VLOCK IS OFF OUTSIDE OF $VSYNHR PLUS 18 SECOND
(0.005 HOUR) WINDOW
00998C ON FIRST PASS LOCKOUT IS TURNED ON AND SUBROUTINES
ACCESSED
01000IF($VHOUR.EQ.$VSYNHR.AND.($VCRTM-$VHOUR).LT.0.005) THEN
GOTO 1030
01010OFF($VLOCK)
01020GOTO 1990
01030IF($VLOCK.EQ.OFF) THEN GOTO 1050
01040GOTO 1990
01050ON($VLOCK)
01054C
01056C ENTER A GOSUB FOR EACH PXC COMPACT ON P1 WITH TIME HOSTED
BY THIS FIELD PANEL
01058C SUBROUTINE SYNCHRONIZES TIME ONCE DAILY AT $VSYNHR
01060GOSUB 2100 "B2.AHU1:SYNC HOUR", "B2.AHU1:SYNC NOW"
Working at the Host Field
Panel

Table of Contents

Other manuals for Siemens PXC Modular Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PXC Modular Series and is the answer not in the manual?

Siemens PXC Modular Series Specifications

General IconGeneral
BrandSiemens
ModelPXC Modular Series
CategoryControl Unit
LanguageEnglish

Related product manuals