Hardware Features
Communication Connections
36
| 100
Siemens Industry, Inc.
145-172
Building Technologies
Restricted
2018-09-25
Standard RJ-45 (8-pin) Tool Socket for RS-232 Devices.
Pin
Description
Pin
Description
1 Not connected 5 Not connected
2 Not connected 6 RxD
3 Ground 7 TxD
4 24 Vdc 8 Not connected
10B/100B Ethernet Port
The 10B/100B Ethernet port provides a path for commands and information
transmitted between field panels inside a firewall. This port provides both full- and half-
duplex 10Base-T or 100Base-TX compliant communications over a BACnet/IP or
Ethernet TCP/IP (P2) Automation Level Network (ALN). The highest possible
communication speed is automatically detected and selected.
RS-485 Port
The RS-485 port provides a path for commands and information transmitted between
field panels. This port provides communications over a RS-485 P2 or BACnet MS/TP
Automation Level Network (ALN) or P1 or MS/TP Field Level Network (FLN). The
communication speed is set during startup.
The RS-485 port provides half-duplex, asynchronous serial RS-485 communications
over shielded twisted pair cable. The RS-485 connector is labeled + to indicate the
positive and negative connections; is a reference pin.
The PXC-36 provides two RS-485 ports, which are labeled “A” and “B”.
All PXC-36 models and the PXC-16 and PXC-24 "F" models support P1 or MS/TP
FLN devices on the RS-485 port.
BACnet MS/TP routed FLN is supported for Programmable TECs (PTECs), Unitary
Equipment Controllers (UECs), and third-party BACnet devices.
FIN Builder supports MS/TP routed FLNs and IP FLNs.
PPCL and Point Editing are currently not available on routed FLNs.
When the PXC Compact Series is operating in P1 Mode (PXC-16 and PXC-24
only), the RS-485 port connects the PXC Compact to a P1 FLN where it emulates
a TEC.
When communicating on an RS-485 ALN, the Virtual AEM may be used to
communicate with a P2 Ethernet network.

Table of Contents

Other manuals for Siemens PXC Modular Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PXC Modular Series and is the answer not in the manual?

Siemens PXC Modular Series Specifications

General IconGeneral
BrandSiemens
ModelPXC Modular Series
CategoryControl Unit
LanguageEnglish

Related product manuals