EasyManuals Logo
Home>Siemens>Control Unit>PXC Modular Series

Siemens PXC Modular Series User Manual

Siemens PXC Modular Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
Service Information
Troubleshooting the TX-I/O Island Bus
99 |
100
Technical Reference Manual
145-172
Restricted
2018-09-25
1. Working on the adjacent TX-I/O module on the male bus connecter, swivel the
address key out of the plug-in module.
Leave the base of the key plugged into the terminal base.
2. Remove the adjacent I/O module from its terminal base.
3. Working on the TX-I/O module being removed, pull the mounting tabs outward.
4. Remove the complete TX-I/O module assembly (plug-in module and terminal
base).
Removing the terminal base interrupts the Island Bus communication and
power.
5. Insert the new TX-I/O module assembly without an address key.
6. Push in the mounting tabs on the terminal base.
7. Move the address key from the old module to the new one and swivel it into
position.
8. Plug the adjacent I/O module back into its terminal base, and swivel the address
key back into position.
As soon as the new module starts communicating with the PXC Modular, PXC-36,
or P1 BIM, it is configured according to the module address and starts operation
shortly afterward.

Table of Contents

Other manuals for Siemens PXC Modular Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens PXC Modular Series and is the answer not in the manual?

Siemens PXC Modular Series Specifications

General IconGeneral
BrandSiemens
ModelPXC Modular Series
CategoryControl Unit
LanguageEnglish

Related product manuals