HRX-OM-X010
Chapter 3 Transporting and Installation
3.2 Installation HRZ Series
3-4
3.2.1 Installation conditions
System installation is not allowed outside or in the conditions described below.
Potential system malfunction and damage may occur if disregarded.
Clean room specifications are not applied to this unit. The pump and ventilating
fan installed in this unit generate particles.
Location that is exposed to water vapor, salt water, and oil
Location that is exposed to dust and powder
Location that is exposed to corrosive gas, solvent, and flammable gas
Location that is exposed to direct sun light or radiant heat
Location where ambient temperature is out of the following range:
In operation 10 to 35 deg C
In storage 0 to 50 deg C(with no water or circulating fluid in piping)
Location where relative humidity is out of the following range:
In operation 30 to 70%
In storage 15 to 85%
Location that is subjected to abrupt changes in temperature
Location that is subjected to intense electromagnetic noise (intense electric field,
intense magnetic field, or surges)
Location that is subjected to static electricity, or condition that discharges static
electricity to the system
Location that is subjected to strong high frequencies
Location that is subjected to potential lightning damage
Location with altitudes of 1000m or higher
Location that is affected by strong vibrations or impacts
Condition that applies external force or weight causing the system deformation
Condition with no adequate space for maintenance as required in the installation
site.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRZ002-WS-F and is the answer not in the manual?

SMC Networks HRZ002-WS-F Specifications

General IconGeneral
BrandSMC Networks
ModelHRZ002-WS-F
CategoryChiller
LanguageEnglish

Related product manuals