HRX-OM-X010
Chapter 3 Transporting and Installation
3.3 Procedure for Installation HRZ Series
Anti-seismic bracket is an optional part (except for HRZ008-L-F, HRZ008-L1-F), which is required
for the installation of this system (HRZ-TK002).
Preparation of anchor bolts suitable for floor material is your responsibility. M8-anchor bolts (8
pcs.) are required for HRZ008-L-F and HRZ008-L1-F, and M12-anchor bolts (4 pcs.) for other
models. See “Appendix 8.6 Anchor Bolt Mounting Position”on page 8-18.
3.3 Procedure for Installation
3.3.1 Installation
System installation should be on a vibration-free stable level plane.
See “Appendix 8.2 Outer Dimensions” in Chapter 8 on page 8-11 for the
dimensions of this system.
3.3.2 Procedure for system securing (1)
HRZ***-WS-F HRZ***-W1S-F HRZ***-W2S-F
1. Transfer this system to the installation site.
2. Lock the brakes on casters (2 pcs. on the front).
3. Using a13-mm open end wrench, attach the anti-seismic brackets to the front and back.
Figure 3-4 Anti-seismic Bracket Attachment
Drain pan port is assigned to the bottom on the back of this system. Exercise
caution not to damage the dain pan port when attaching the anti-seismic bracket.
Anti-seismic bracket (optional)
HRZ-TK002
M8 nut (2 pcs.)
(Accessory for anti-seismic
bracket)
Caster w/ brake
(2 pcs. on the front)