HRX-OM-X010
Chapter 8 Appendix
HRZ Series 8.4 Offset Function
8-15
8-15
8.4.1 Example of offset function
When the discharge temperature of the circulating fluid is at 30deg C, heat is
dissipated by 1deg C to allow the circulating fluid in your system to be 29deg C.
Under the above condition, the following process is to be performed with the
utilization of MODEs 1 to 3.
Figure 8-5 Example of Offset Function
When MODE1 is selected
This mode enables this system to exercise temperature control to obtain 31deg C
(TEMP SP value +OFFSET value), with OFFSET value set at 1deg C. Once the
discharge temperature of the circulating fluid becomes 31deg C, 1deg C-thermal
dissipation is assured to allow the circulating fluid in your system to be 30deg C.
TEMP SP value is obtained for your system.
Note that “31deg C” is recorded in TEMP PV and communication data.
Figure 8-6 When MODE1 is selected
This system
Your system
Discharge temp.:
30
Circulating fluid temp. in
your system: 29
TEMP PV 30
deg C
TEMP SP 30
External communication
Communication data
TEMP PV 30
Heat dissipation:
deg C
deg C
deg C
1deg C
deg C
1deg C
This system
Your system
Discharge temp.:
31
Circulating fluid temp. in
your system: 30
deg C
TEMP PV 31
TEMP SP 30
OFFSET 1
External communication
Communication data
TEMP PV 31
TEMP PV
31
Heat dissipation:
deg C
deg C
deg C
deg C
deg C
deg C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRZ002-WS-F and is the answer not in the manual?

SMC Networks HRZ002-WS-F Specifications

General IconGeneral
BrandSMC Networks
ModelHRZ002-WS-F
CategoryChiller
LanguageEnglish

Related product manuals