HRX-OM-X010
Chapter 8 Appendix
HRZ Series 8.5 BAND/READY function
8-17
8-17
8.5 BAND/READY function
Sets BAND to TEMP SP value, and notifies TEMP PV value reaches within
BAND range by the operation display panel or the communication.
See section Chapter 5 System Operation 5.3.21 Initial Setting screen 6 on page
5-23,for the procedure of the setting.
When the setting is ON
Allows the setting of the BAND and REDY TIME. Allows the setting of the
communication output.
Figure 8-9 BAND/READY function
Examples of Setting
TEMP SP20deg C
BAND2deg C
READY TIME60sec.
TEMP READY is displayed on the operation display panel 60-sec. after
TEMP PV value becomes 18 deg C to start output by communication.
Necessary condition is that TEMP PV value after 60-sec. is 20+/-2.0 deg C
or less. See 5.3.4 Status screen 3 on page 5-7 for the details of display
position.
When the setting is OFF
BAND/READY function becomes invalid.
BAND
TEMP SP
TEMP PV
TEMP READY not display/not output
TEMP READY display/output
READY
TIME

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRZ002-WS-F and is the answer not in the manual?

SMC Networks HRZ002-WS-F Specifications

General IconGeneral
BrandSMC Networks
ModelHRZ002-WS-F
CategoryChiller
LanguageEnglish

Related product manuals