A.2 Single/Three-Phase 200 V Class Drive
Table A.2 Power Ratings
Item Specification
Three-Phase: CIMR-Jo2A
0001 0002 0004 0006 0008 0010 0012 0018 0020
Single-Phase: CIMR-JoBA
<1>
0001 0002 0003 0006 - 0010 - - -
Maximum Motor Size Allowed
(kW)
<2>
ND Rating 0.2 0.4 0.75 1.1 1.5 2.2 3.0 3.7 5.5
HD Rating 0.1 0.2 0.4 0.75 1.1 1.5 2.2 3.0 3.7
Input
Input
Current (A)
<3>
Three-
Phase
ND Rating 1.1 1.9 3.9 7.3 8.8 10.8 13.9 18.5 24.0
HD Rating 0.7 1.5 2.9 5.8 7.0 7.5 11.0 15.6 18.9
Single-
Phase
ND Rating 2.0 3.6 7.3 13.8 – 20.2 - – –
HD Rating 1.4 2.8 5.5 11.0 – 14.1 - – -
Output
Rated Output Capacity
(kVA)
<4>
ND Rating 0.5 0.7 1.3 2.3 3.0 3.7 4.6 6.7 7.5
HD Rating 0.3 0.6 1.1 1.9 2.6 3.0 4.2 5.3 6.7
Output Current (A)
ND Rating
<5>
1.2 1.9
3.5
(3.3)
6.0 8.0 9.6 12.0 17.5 19.6
HD Rating
0.8
<6>
1.6
<6>
3.0
<6>
5.0
<6>
6.9
<7>
8.0
<7>
11.0
<7>
14.0
<7>
17.5
<7>
Overload Tolerance
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
(Derating may be required for applications that start and stop
frequently)
Carrier Frequency 2 kHz (user-set, 2 to 15 kHz)
Max Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage)
Max Output Frequency (Hz) 400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: Three-phase 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
Harmonic Corrective
Actions
DC Reactor Optional
<1> Drives with a single-phase power supply input
output three-phase power, and cannot run a single-phase motor.
<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated
input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0”
for HD or “1” for ND (default).
A.2 Single/Three-Phase 200 V Class Drive
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
189
A
Specifications
2/6/2008-14:44