2.2 Mechanical Installation
This section outlines specifications, procedures, and environment for proper mechanical
installation of the drive.
u
Installation Environment
To help prolong the optimum performance life of the drive, install the drive in the proper
environment. The table below provides a description of the appropriate environment for the
drive.
Table 2.1 Installation Environment
Environment Conditions
Installation Area Indoors
Ambient
Temperature
-10 °C to +50 °C (IP20/Open-Chassis)
Drive reliability improves in environments without wide temperature fluctuations.
When using an enclosure panel, install a
cooling fan or air conditioner in the area to ensure that
the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20 °C to +60 °C
Surrounding Area
Install the drive in an area free from:
oil mist and dust
metal shavings, oil, water or other foreign materials
radioactive materials
combustible materials (e.g., wood)
harmful gases and liquids
excessive vibration
chlorides
direct sunlight
Altitude 1000 m or lower
Vibration
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
2
Orientation Install the drive vertically to maintain maximum cooling effects.
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during
installation and project construction. Failure to comply
could result in damage to the drive. Place a temporary
cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover
will reduce ventilation and cause the drive to overheat.
2.2 Mechanical Installation
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
33
2
Mechanical Installation
2/6/2008-14:44

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-JA Series and is the answer not in the manual?

YASKAWA CIMR-JA Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-JA Series
CategoryController
LanguageEnglish

Related product manuals