A.5 Drive Watt Loss Data
Table A.4 Watt Loss 200 V Class Single-Phase Models
Model
Number
CIMR-Jo
Heavy Duty (Carrier Frequency 8 kHz) Normal Duty (Carrier Frequency (2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
BA0001 0.8 4.3 7.4 11.7 1.2 5.0 8.5 13.5
BA0002 1.6 7.9 8.9 16.7 1.9 7.6 9.7 17.3
BA0003 3.0 16.1 11.5 27.7 3.2 14.6 14.4 29.1
BA0006 5.0 33.7 16.8 50.5 6.0 30.1 19.4 49.5
BA0010 8.0 54.8 25.9 80.7 9.6 51.7 29.8 81.4
Table A.5 Watt Loss 200 V Class Three-Phase Models
Model
Number
CIMR-Jo
Heavy Duty (Carrier Frequency 8 kHz) Normal Duty (Carrier Frequency 2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
2A0001 0.8 4.3 7.3 11.6 1.2 5.0 8.0 13.0
2A0002 1.6 7.9 8.8 16.7 1.9 7.6 9.5 17.1
2A0004 3.0 16.2 11.5 27.7 3.5 15.8 13.6 29.4
2A0006 5.0 27.4 15.9 43.3 6.0 27.5 17.2 44.7
2A0008 7.0 48.7 22.2 70.9 8.0 44.6 24.0 68.6
2A0010 8.0 54.8 23.8 78.6 9.6 51.7 25.8 77.5
2A0012 11.0 70.7 29.9 100.6 12.0 61.3 30.4 91.7
2A0018 14.0 92.6 38.8 131.4 18.0 89.8 44.1 133.8
2A0020 17.5 110.5 43.3 153.8 19.6 98.7 46.3 145.0
Table A.6 Watt Loss 400 V Class Three-Phase Models
Model
Number
CIMR-Jo
Heavy Duty (Carrier Frequency 8 kHz) Normal Duty (Carrier Frequency 2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
4A0001 1.2 19.2 11.5 30.7 1.2 10.0 9.6 19.6
4A0002 1.8 28.9 14.8 43.7 2.1 18.5 13.9 32.4
4A0004 3.4 42.3 17.9 60.2 4.1 30.5 16.8 47.3
4A0005 4.8 70.7 26.2 96.9 5.4 44.5 21.8 66.3
4A0007 5.5 81.0 30.7 111.7 6.9 58.5 28.4 86.9
4A0009 7.2 84.6 32.9 117.5 8.8 63.7 31.4 95.1
4A0011 9.2 107.2 41.5 148.7 11.1 81.7 46.0 127.7
A.5 Drive Watt Loss Data
194
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2/6/2008-14:44

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-JA Series and is the answer not in the manual?

YASKAWA CIMR-JA Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-JA Series
CategoryController
LanguageEnglish

Related product manuals