4.5 Basic Operation
This section explains the basic settings required for initial drive operation. Checking these
basic parameter settings during start-up will help to ensure a successful drive start-up.
If more information is required for parameters
not listed in this section, Refer to Parameter
List on page 197 as required for a complete listing of drive parameters.
u
Initialize Parameter Values: A1-03
Parameter A1-03 (Initialize Parameters) resets all parameters to the original default values.
Note: Record all the changed settings before initializing parameters.
n
Different Methods of Drive initialization
2220: 2-Wire Initialization
Returns all parameters to factory default values for 2-wire control.
3330: 3-Wire Initialization
Returns all parameters to factory default values for 3-wire control.
u
Frequency Reference Source: b1-01
This section explains how to assign the frequency reference. Parameters b1-01 and b1-02 can
be used to select the source of the run command and the frequency reference independently
(e.g., set the reference from the operator and set the run command from the terminals).
n
Frequency Reference from the LED Operator: b1-01 = 0
When b1-01 = 0 the frequency reference will be provided by the LED operator. Refer to The
Drive and Programming Modes on page 78 for information on how to set the frequency
reference.
n
Frequency Reference from the Analog Input Terminal: b1-01 = 1
When b1-01 = 1, analog input A1 provides the frequency reference.
Note: Set H3-01 (Terminal A1 Function Selection) to “0” to configure Terminal A1 for the main analog frequency
reference.
Voltage Input
When entering the frequency reference with a voltage signal, set parameter H3-01 to “0” for
0 to 10 Vdc with lower reference limit. Set H3-01 to “1” if 0 to 10 Vdc input without lower
limit is required. Set DIP Switch S1 for voltage input (position “V”).
4.5 Basic Operation
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
87
4
Start-Up Programming