3.6 Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and
properly wire the main circuit of the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen
over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
u
Main Circuit Terminal Functions
Table 3.1 Main Circuit Terminal Functions
Terminal Type Function Reference
R/L1
Main circuit power
supply input
Connects line power to the drive.
Drives with single-phase 200 V input power
use terminals R/L1 and
S/L2 only (T/L3 must not be used).
46S/L2
T/L3
U/T1
Drive output Connects to the motor. 52V/T2
W/T3
B1
Braking resistor
Available for connecting a braking resistor or the braking resistor
unit option.
65
B2
+1
DC reactor
connection
These terminals are shorted at shipment. Remove the shorting bar
between +1 and +2 when connecting to this terminal.
173
+2
+1
DC power supply
input
For connecting a DC power supply.
(2 terminals)
Ground
Grounding Terminal
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less
52
u
Wire Gauges and Tightening Torque
Select the appropriate wires and crimp terminals from Table 3.2 through Table 3.4.
Note: 1. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-
sheathed wire assuming ambient temperature within 30 °C and wiring distance less than 100 m.
2. Terminals +1, +2, –, B1 and B2 are for connecting optional devices such as a DC reactor or braking
resistor. Do not connect other non-specified devices to these terminals.
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge
when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is
suitable for the terminal block. Use the following formula to calculate the amount of voltage
drop:
Line drop voltage (V) = 3 x wire resistance (Ω/km) x wire length (m) x current (A) x
10
-3
Refer to instruction manual TOBPC72060000 for braking
unit or braking resistor unit wire
gauges.
Refer to UL Standards Compliance on page 236 for information on UL compliance.
3.6 Main Circuit Wiring
50
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2/6/2008-14:44

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-JA Series and is the answer not in the manual?

YASKAWA CIMR-JA Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-JA Series
CategoryController
LanguageEnglish

Related product manuals