4.3 The Drive and Programming Modes
The drive functions are divided into two
main groups accessible via the Digital LED Operator:
Drive Mode: The Drive mode allows motor operation and parameter monitoring. Parameter
settings cannot be changed when accessing functions in the Drive Mode (Table 4.3).
Programming Mode: The Programming Mode allows access to setup/adjust, verify
parameters. The drive prohibits changes in motor operation such as start/stop when the Digital
LED Operator is accessing a function in the Programming Mode.
Table 4.3 illustrates the different functions visible as the “Up arrow” is scrolled immediately
after powering up the drive.
Note: When b1-08 (Run Command Selection while in Programming Mode) is set to 1 (enabled), the drive can run
even if the mode is switched to the programming mode. When setting b1-08 to 0 (disabled), the mode cannot
be switched to the programming mode while the drive is running.
Table 4.3 Summary of Modes
Mode Group Description Key Press LED Digital Operator Display
Drive Mode Functions
(Motor operation and
monitoring)
Frequency Reference Display
(Initial power-up state)
Forward/Reverse
Output Frequency Display
Output Current Display
Output Voltage Reference
Monitor Display
Programming Mode Functions
(Changing parameters)
Verify Function
Setup Group Parameters
All Parameters
u
Navigating the Drive and Programming Modes
The drive is set to operate in
Drive Mode when it is first powered up. Switch between display
screens by using the
and keys.
4.3 The Drive and Programming Modes
78
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2/6/2008-14:44