No. Name Description Range Def.
Mode
Addr.
Hex
Pg.
V/f
b1-03
Stopping
Method
Selection
Selects the stopping method when the run command
is removed.
0: Ramp to Stop
1: Coast to Stop
0, 1 0 S 182 91
b1-04
Reverse
Operation
Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0, 1 0 O 183 —
b1-07
LOCAL/
REMOTE Run
Selection
Determines the operation when the Run command
source is switched from LOCAL to REMOTE or
between Run source 1 and 2 while an external Run
command is active at the new source.
0: External Run command has to be
cycled at the new
source to be activated.
1: External Run command at new source is accepted
immediately.
0, 1 0 O 186 —
b1-08
Run Command
Selection while
in
Programming
Mode
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
0 to 2 0 O 187 —
b1-14
Phase Order
Selection
Sets the phase order for drive output terminals U/T1,
V/T2 and W/T3.
0 : Standard
1 : Switch phase order
0, 1 0 O 1C3 —
b1-17
Run Command
at Power Up
Determines the operation when a Run command is
active at power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0, 1 0 O 1C6 —
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
b2-02
DC Injection
Braking
Current
Sets the DC Injection Braking current as a percentage
of the drive rated current.
0 to 75 50% O 18A —
b2-03
DC Injection
Braking Time/
DC Excitation
Time at Start
Sets DC Injection Braking time at start. Disabled
when set to 0.00 seconds.
0.00 to
10.00
0.00 s O 18B —
b2-04
DC Injection
Braking Time
at Stop
Sets DC Injection Braking time at stop.
When b1-03 = 0, this parameter sets
the amount of DC
Injection time applied to the motor at the end of the
decel ramp. Disabled when set to 0.00.
0.00 to
10.00
0.50 s O 18C —
B.2 Parameter Table
200
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2/6/2008-14:44