2-22 (28) 2UEA001270 Rev. F ACS2000 User manual
Chapter 2 - Power electronics and cabinet features
2.4.2 Main power supply configuration
The ACS2000 4 kV drive includes an input filter unit which enables the
drive to be connected directly to the 4160 V main power supply as shown
in Figure 2-18. For drives with the integral input contactor disconnect, the
power fuses are relocated to the switchgear, see Appendix P for details.
See Appendix P - Integral Input Contactor Disconnect, located on the CD,
for main power supply configuration and details on the TEU when the drive
is ordered with this option.
Figure 2-18 Single-line diagram with direct-to-line configuration
2.4.3 Power fuses
There are three semiconductor rated power fuses located in the TEU for
the purpose of providing input protection for the drive.
Note: On drives with the integral input contactor disconnect option, the
fuses are located in the disconnect cabinet.
Table 2-4 Power fuse ratings
Legend
1 Fuse
2 Input filter unit
1
Main
power
supply
ACS2000
Drive system
M
MV
switch-
gear
2
Drive rating
kW [hp]
Current rating
(A)
ABB
part number
Quantity
per phase
Frame 1
224-298 [300-400] 80 2UEA001267 1
336-522 [450-700] 140 2UEA001268 1
597-746 [800-1000] 200 2UEA000093 1
Frame 2
933 [1250] 140 2UEA001268 2
1119-1492 [1500-2000] 160 2UEA002203 2
Frame 3
1679-2238 [2250-3000] 230 2UEA001947 2