3-18 (26) 2UEA001270 Rev. F ACS2000 User manual
Chapter 3 - Control system
3.3.2.3 IOEC2 (A1541) analog inputs
Table 3-6 Standard analog input signal allocation
3.3.2.4 IOEC2 (A1541) analog outputs
Table 3-7 Standard analog output signal allocation
Terminal Channel Default setting Par. Group
X31-1 +10 V
0 V
Internal supply voltage —
X32-1
X31-2 AI1+
AI1-
Reference value 1 (speed reference)
X32-2
X31-3 AI2+
AI2-
Reference value 2
(speed or torque reference)
X32-3
X31-4 AI3+
AI3-
Motor winding V temperature
X32-4
X31-5 AI4+
AI4-
Motor winding W temperature
X32-5
Remote speed supply
output specifications
Output voltage 10 V
Available output current 5mA
Analog input resolution 10 bit
Voltage mode Current mode
Signal range
0...10 V
Signal range
0...20mA
Load impedance
250 kΩ
Load impedance
105 Ω
S1
S2
AI1 20m
AI1 10 V
AI2 20m
AI2 10 V
OFF
ON
AI3 20m
AI3 10 V
AI4 20m
AI4 10 V
S1
S2
AI1 20mA
AI1 10 V
AI2 20mA
AI2 10 V
OFF
ON
AI3 20mA
AI3 10 V
AI4 20mA
AI4 10 V
X31-1
X32-4
X32-1
X31-2
X32-2
X31-3
X32-3
X31-4
X31-5
X32-5
+10 V
0 V
AI1+
Wiring example - remote speed
Internal supply voltage
Remote
speed
control
Terminal Channel Default setting Par. Group
X31-6 AO1+
AO1-
Motor speed act
X32-6
X31-7 AO2+
AO2-
Motor torque act filt
X32-7
Analog output resolution 12 bit
Signal level
0...20mA
Load impedance
250 Ω