ACS2000 User manual 2UEA001270 Rev. F 3-21 (26)
Chapter 3 - Control system
3.3.3.2 IOEC4 (A1621) digital inputs
Table 3-9 Optional digital input signal allocation
Terminal Channel Default setting Par. Group
X11-1 DI01 Freely programmable
X11-2 Common
X11-3 DI02 Freely programmable
X11-4 Common
X11-5 DI03 Freely programmable
X11-6 Common
X11-7 DI04 Freely programmable
X11-8 Common
X11-9 DI05 Freely programmable
X11-10 Common
X12-1 DI06 Freely programmable
X12-2 Common
X12-3 DI07 Freely programmable
X12-4 Common
X12-5 DI08 Freely programmable
X12-6 Common
X12-7 DI09 Freely programmable
X12-8 Common
X12-9 DI10 Motor protection monitoring
X12-10 Common
X13-1 DI11 Motor vibration 2/bearing 2 (alarm trip)
X13-2 Common
X13-3 DI12 Motor vibration 1/bearing 1 (alarm trip)
X13-4 Common
X13-5 DI13 Ext mot trip (ovrtmp/ovrspd/space htr/fan)
X13-6 Common
X13-7 DI14 External motor alarm
X13-8 Common
X13-9 +24 V
+0 V
24 V control logic
X13-10 Common
Current
Signal level direct Typ 24 VDC
max 100 VDC
Signal level
alternating
Typ 24 VAC
max 230 VAC
Input 8...25mA
Inrush 24 V 10mA
Inrush 120 V Typ 65mA
max 100mA