Program features 59
The ID of the application licence is displayed by DriveStudio in the drive software
properties as APPL LICENCE. If the value is 0, no licence has been assigned to the
drive.
Notes:
• The application licence can only be assigned to a complete drive, not a stand-
alone control unit.
• A protected application can only be downloaded to a complete drive, not a stand-
alone control unit.
Control interfaces
îš„ Programmable analog inputs
The drive has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a jumper on the JCU Control Unit. Each input can be filtered, inverted and
scaled. The number of analog inputs can be increased by using FIO-xx I/O
extensions.
Settings
Parameter group 13 Analogue inputs (page 135).
îš„ Programmable analog outputs
The drive has two current analog outputs. Each output can be filtered, inverted and
scaled. The number of analog outputs can be increased by using FIO-xx I/O
extensions.
Settings
Parameter group 15 Analogue outputs (page 155).
îš„ Programmable digital inputs and outputs
The drive has six digital inputs, a digital start interlock input, and two digital input/
outputs.
One digital input (DI6) doubles as a PTC thermistor input. See section Thermal motor
protection on page 80.
One of the digital input/outputs can be used as a frequency input, one as a frequency
output.
The number of digital inputs/outputs can be increased by using FIO-xx I/O
extensions.