192 Parameters
27.23 Sleep level Defines the start limit for the sleep function. If the motor
speed is below this value longer than the sleep delay (27.24
Sleep delay), the drive shifts to the sleep mode.
-32768.0 …
32768.0 rpm
Sleep start level. 10 = 1 rpm
27.24 Sleep delay Defines the delay for the sleep start function. See parameter
27.23 Sleep level. When the motor speed falls below the
sleep level, the counter starts. When the motor speed
exceeds the sleep level, the counter resets.
0.0 … 360.0 s Sleep start delay. 10 = 1 s
27.25 Wake up level Defines the wake-up limit for the sleep function. The drive
wakes up if the process actual value is above the wake-up
level longer than the wake-up delay (27.26 Wake up delay).
0.0 … 32768.0 Wake-up level. 10 = 1
27.26 Wake up delay Defines the wake-up delay for the sleep function. See
parameter 27.25 Wake up level. When the process actual
value falls below the wake-up level, the wake-up counter
starts. When the process actual value exceeds the wake-up
level, the counter resets.
0.0 … 360.0 s Wake-up delay. 10 = 1 s
27.27 Sleep ena Defines a source that can be used to activate sleep mode
when parameter 27.22 Sleep mode is set to External.
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
DI6 Digital input DI6 (as indicated by 02.01 DI status, bit 5). 1074070017
Const Bit pointer setting (see Terms and abbreviations on page
102).
-
Pointer
30
30 Fault functions
Selects the behavior of the drive upon various fault situations.
30.01 External fault Selects an source for an external fault signal.
0 = External fault trip
1 = No external fault
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
DI6 Digital input DI6 (as indicated by 02.01 DI status, bit 5). 1074070017
DIO4 Digital input/output DIO4 (as indicated by 02.03 DIO status,
bit 3).
1073938947
DIO5 Digital input/output DIO5 (as indicated by 02.03 DIO status,
bit 4).
1074004483
DIO6 Digital input/output DIO6 (as indicated by 02.03 DIO status,
bit 5).
1074070019
No. Name/Value Description FbEq