Planning the electrical installation
46
3ADW000462R0301 DCS880 Hardware Manual e c
Fan Data for DCS880 (H1 ... H4)
Fan connection for DCS880 (H1 ... H4)
Fan 3110UL AFB122 W2E200 W2E200 W2E250 W2E250
Rated voltage [V
AC
] 24 V intern 24 V intern 230; 1~ 115; 1~ 115; 1~ 230; 1~
Tol e rance [%] +6 / -10 +6 / -10 ±10 +6 / -10
Frequency [Hz] 50 60 50 60 50 60 50 60
Power consumption [W] 64 80 64 80 120 165 135 185
Current consumption [A] 0.29 0.35 0.6 0.7 1.06 1.44 0.59 0.82
Blocking current [A] < 0.7 < 0,8 < 1.5 < 1.8 < 1.8 < 1.8 < 0.9 < 0.9
Air flow [m
3
/h] freely blowing 50 190 925 1030 925 1030 1835 1940 1860 1975
Max. ambient temperature [° C] < 70 < 70 < 75 < 75 60 60
Useful lifetime of grease 70,000
h/25°
100,000
h/25°
appr.
45,000 h/60°
appr.
45,000 h/60°
appr.
40,000 h
appr.
40,000 h
Protection Internal temperature detectors
|---------------------------------------------------------- Terminals are located on top of the converter housing ---------------------------------------------|
Converter housing
Configuration 1
H1
Configuration 2
H2 ... H3
Configuration 3
H3
Configuration 4
H4
M
PIN-H01
24 V internal
PIN-H01
24 V internal
M
M55 M56
M M
M55 M56
M M
M57 M58
M55
M
~
12 345X52:
LN
L
N
J
SA_880_011_DCS_FAN_c.ai
M
_____
__
X41: 1 2 X41: 1 2 X42: 1 2 X41: 1 2 X43: 1 2 X42: 1 2 X44: 1 2
PIN-H01
24 V internal
M55
+ - + - + - + - + - + - + -
either 230 V
AC
or 115 V
AC