Planning the electrical installation
47
3ADW000462R0301 DCS880 Hardware Manual e c
Fan data for DCS880 (H5 ... H8)
The fan needs an input voltage of 400 V
AC
at 50 Hz. For 460 V
AC
/ 500 V
AC
use autotransformer
(T8).
The fan needs an input voltage of 460 V
AC
at 60 Hz. For 500 V
AC
use autotransformer (T8).
Fan connection for DCS880 (H5 ... H8)
Fan R2E250-RB GR28C-2DK GR35C-2DD
Rated voltage [V
AC
] 230; 1~ 400
500
460 400 / 460 /
500 V
460 /
500 V
Tolerance [%] ±10 ±10 ±10 ±10
Frequency [Hz] 50 60 50 60 50 60
Power consumption [W] 227 390 660
600
1100 2100 3000
Current consumption [A] 1.1 1.7 1.4
0.8
1.8 4.0 5.3
Blocking current [A] 3.1 3.1 at 400 V 8.0
at 500 V 2.8
at 460 V 8.0 at 400 V > 17 at 460 V > 15
Air flow [m
3
/h]
at working point
800
1.0 A
850
1.6 A
1600 @ 1.2 A
(400 V )
1500 @ 0.7 A
(500 V )
1700 @ 1.6 A
(460 V )
4200 @ 4 A
(400 V)
4500 @ 5.3 A
(400 V)
Max. ambient temperature [°C] < 55 < 55
Useful lifetime of grease appr. 40,000 h/40°C appr. 30,000 h/40°C
Protection internal Temperature detector: U
N
230 V~; I
N
2.5 A~
Converter housing
Configuration 5
H5, H6
Configuration 6
H7
Configuration 7
H8
U1 V1 W1 U2 V2 W2 TK TKPE
at
U1-W2
V1-U2
W1-V2
M
~
J
U1 V1 W1U2 V2W2PE TB TB
at
M
~
U1 V1 W1U2 V2W2PE TB TB
at
U2 - V2 - W2
M
~
U1-W2
V1-U2
W1-V2
M
~
231X2:
4 5
LN
SA_880_011_DCS_FAN_b.ai
Connection
Connection
Connection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DCS880 H1 and is the answer not in the manual?

ABB DCS880 H1 Specifications

General IconGeneral
Rated currentUp to 5200A
Enclosure classIP00, IP21, IP54
MountingCabinet-mounted
Fieldbus communicationCANopen
SafetySTO (Safe Torque Off)
Output currentUp to 5200A
Communication protocolsPROFIBUS DP, CANopen
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Enclosure ratingIP00, IP21, IP54
Cooling methodAir or liquid cooling

Related product manuals