EasyManuals Logo
Home>ABB>Controller>MRP31.0

ABB MRP31.0 User Manual

ABB MRP31.0
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
Function Overview
Protection Function voltage  Available Options:

Automatic Fault
Reset Possible
Overvoltage:
The highest value of the three phases is above a given
threshold.
The warning - and trip thresholds as well as the according
delays can be set.
Motor running
Motor stopped
Not in test position
Trip, Warning, Off -
Undervoltage:
The lowest value of the three phases is below a given
threshold.
The warning - and trip thresholds as well as the according
delays can be set.
Motor running
Motor stopped
Not in test position
Trip, Warning, Off -
Voltage Dip:
Low voltage situation which requires an
autonomous load sheeding
handling should take place in the UMC.
After motor start
Not in test position
Reaction depends on Dip
duration.
-
Phase loss:
In opposite to the current based phase loss protection
function this function detects a missing phase also in the
case the motor is stopped.
A warning / trip can be signalled before the motor is actually
started i.e. to detect a blown fuse.
Motor running
Motor stopped
Not in test position
Trip, Warning, Off
-
Voltage imbalance:
This function can be used to detect smaller voltage
imbalances between the phases.
Warning - and trip thresholds as well as warning - and trip
delays can be set.
Motor running
Motor stopped
Not in test position
Trip, Warning, Off Yes, see parameter
'Fault auto reset'
Total harmonic distortion:
This function measures harmonic distortions in the
connected mains.
Motor running
Motor stopped
Not in test position
Warning -
Overload:
The active power drawn by the motor is too high. The
warning - and trip thresholds as well as the according delays
can be set.
After load start
Not in test position
Trip, Warning, Off -
Underload:
The active power drawn by the motor is too low. The
warning - and trip thresholds as well as the according delays
can be set.
After load start
Not in test position
Trip, Warning, Off -
Cos phi:
A measure of the phase angle between voltage and current.
The warning - and trip thresholds as well as the according
delays can be set.
After load start
Not in test position
Trip, Warning, Off -
50
UMC100.3 UNIVERSAL MOTOR CONTROLLER TECHNICAL DESCRIPTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB MRP31.0 and is the answer not in the manual?

ABB MRP31.0 Specifications

General IconGeneral
BrandABB
ModelMRP31.0
CategoryController
LanguageEnglish

Related product manuals