EasyManuals Logo
Home>ABB>Controller>MRP31.0

ABB MRP31.0 User Manual

ABB MRP31.0
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
Monitoring Data for Pole-Changing Starter
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit1 Bit 0
0
0 Summary
Warning
Summary
Fault
Local Con-
trol
- Overload
warning
Run
Forward
Off -
1 UMC100
DI5
UMC100
DI4
UMC100
DI3
UMC100
DI2
UMC100
DI1
UMC100
DI0
Run
Fast
Forward
-
1 2, 3 Motor Current in % of I
e
(0% - 800%)
2 4, 5
Remaining data see section Parameters and Data Structures on a Fieldbus
3 6, 7
4 8, 9
5 10.11
6
12
13
7
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for
customer-specific applications!
Command Data for Pole-Changing Starter
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit1 Bit 0
0
0 - Fault Reset Auto Mode Prepare
Emergency
Start
- Run
Forward
Off -
1 UMC100
DO2
1)
- - UMC100
24VDC
Out
1)
- - Run
Fast
Forward
-
1
2
Remaining data see section Parameters and Data Structures on a Fieldbus
3
2 4, 5
3 6, 7
1)
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for
customer-specific applications!
85
CONFIGURING THE MOTOR MANAGEMENT FUNCTIONS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB MRP31.0 and is the answer not in the manual?

ABB MRP31.0 Specifications

General IconGeneral
BrandABB
ModelMRP31.0
CategoryController
LanguageEnglish

Related product manuals