Monitoring Data for Actuator 1 - 4
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit1 Bit 0
Summary
Warning
Summary
Fault
Local Control Reverse
Lockout
Time
Overload
warning
Opening Off Closing
- -
Motor Current in % of I
e
Remaining data see section Parameters and Data Structures on a Fieldbus
The table above represents the data allocation as realised with the built-in standard applications. It may differ for
customer-specific applications!
—
Command Data for Actuator 1 - 4
Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit1 Bit 0
- Fault Reset Auto Mode Prepare
Emergency
Start
- Opening Off Closing
- -
- - -
Remaining data see section Parameters and Data Structures on a Fieldbus
1)
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for
customer-specific applications!
90