EasyManuals Logo
Home>ABB>Computer Hardware>TPU2000

ABB TPU2000 User Manual

ABB TPU2000
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
TPU2000/2000R Modbus/Modbus Plus Automation Guide
61
Register
Address
Item Description
3 00116 Reserved Reserved
3 00117 Reserved Reserved
3 00118 Reserved Reserved
3 00119 Reserved Reserved
3 00120 Reserved Reserved
3 00121 Reserved Reserved
3 00122 Reserved Reserved
3 00123 Reserved Reserved
3 00124 Reserved Reserved
3 00125 Reserved Reserved
3 00126 Reserved Reserved
3 00127 Reserved Reserved
3 00128 Reserved Reserved
3 00129 51P-3 Winding 3 Phase Time Overcurrent Alarm Energized
3 00130 50P-3 1
st
Winding 3 Phase Instantaneous Overcurrent Trip Alarm Energized
3 00131 150P-3 2
nd
Winding 3 Phase Instantaneous Overcurrent Trip Alarm Energized
3 00132 51N-3 Winding 3 Neutral Time Overcurrent Alarm Energized
3 00133 50N-3 1
st
Winding 3 Neutral Instantaneous Overcurrent Trip Alarm Energized
3 00134 150N-3 2
nd
Winding 3 Neutral Instantaneous Overcurrent Trip Alarm Energized
3 00135 46-3 Winding 1 Negative Sequence Time Overcurrent Trip Alarm Energized
3 00136 51G Ground Time Overcurrent Control Energized
3 00137 50G 1
st
Ground Time Instantaneous Overcurrent Control Energized
3 00138 150G 2
nd
Ground Time Instantaneous Overcurrent Control Energized
3 00139 51P-3D Winding 3 Phase Time Overcurrent Function Disabled Alarm Energized
3 00140 50P-3D 1
st
Winding 3 Phase Instantaneous Overcurrent Function Disabled Alarm
Energized
3 00141 150P-3D 2
nd
Winding 3 Phase Instantaneous Overcurrent Disable Alarm Energized
3 00142 51N-3D Winding 3 Phase Time Overcurrent Function Disabled Alarm Energized
3 00143 50N-3D 1
st
Winding 3 Neutral Instantaneous Overcurrent Function Disabled
Alarm Energized
3 00144 150N-3D 2
nd
Winding 3 Neutral Instantaneous Overcurrent Disable Alarm Energized
3 00145 46-3D Winding 3 Negative Sequence Tiem Overcurrent Function Disabled Alarm
Energized
3 00146 51GD Ground Time Overcurrent Trip Alarm
3 00147 50GD 1
st
Winding 3 Ground Instantaneous Overcurrent Disable Alarm Energized
3 00148 150GD 2
nd
Winding 3 Ground Instantaneous Overcurrent Disable Alarm Energized
(L) 3 00149 51P-3* Winding 3 Phase Time Overcurrent Alarm Energized Seal In
(L) 3 00150 50P-3* 1
st
Winding 3 Phase Instantaneous Overcurrent Trip Alarm Energized Seal
In
(L) 3 00151 150P-3* 2
nd
Winding 3 Phase Instantaneous Overcurrent Trip Alarm Energized
Seal In
(L) 3 00152 51N-3* Winding 3 Neutral Time Overcurrent Alarm Energized Seal In
(L) 3 00153 50N-3* 1
st
Winding 3 Neutral Instantaneous Overcurrent Trip Alarm Energized
Seal In
(L) 3 00154 150N-3* 2
nd
Winding 3 Neutral Instantaneous Overcurrent Trip Alarm Energized
Seal In
(L) 3 00155 46-3* Winding 1 Negative Sequence Time Overcurrent Trip Alarm Energized
Seal In
(L) 3 00156 51G* Ground Time Overcurrent Control Energized Seal In
(L) 3 00157 50G* 1
st
Ground Time Instantaneous Overcurrent Control Energized Seal In
(L) 3 00158 150G* 2
nd
Ground Time Instantaneous Overcurrent Control Energized Seal In
3 00159 TFKA-3 Through Fault KiloAmps Symmetrical Winding 3
3 00160 HLDA-3 Winding 3 High Level Detector Alarm Energized
3 00161 LLDA-3 Winding 3 Low Level Detector Alarm Energized

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB TPU2000 and is the answer not in the manual?

ABB TPU2000 Specifications

General IconGeneral
BrandABB
ModelTPU2000
CategoryComputer Hardware
LanguageEnglish

Related product manuals