70 TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
… 10 Operation
… Parameter description HART® (for HART®-devices from SW-Rev.: 03.00)
Menu: Calibrate
Select the ‘Measured range’ submenu.
Select the ‘Analog Out’ submenu.
… / Calibrate / Measured range
The current reading (PV) is used as the lower range limit (4 mA).
The current reading (PV) is used as the upper range limit (20
mA).
… / Calibrate / Analog Out
Adjusts the current output with a 4 mA setpoint
range:3.500 to 4.500 mA
Adjusts the current output with a 20 mA setpoint
Value range:19.500 to 20.500 mA
Menu: Diagnosis
Simulates the current output signal
23.600 mA
Diagnostic notice (maintenance required, failure, etc.)
SIL Check’ submenu.
Not passed, chk Tool:Use tool for a detailed check of the current device configuration.
• Passed:SIL Configuration Check successful.The device configuration is valid for SIL Safety applications.
Temp. of Electronics’ submenu.
Drag indicator: maximum or minimum device temperature
Sensor 1 process data’ submenu.
Drag indicator: maximum or minimum sensor temperature for sensor
1
• Reset: Resets the values
Sensor 2 process data’ submenu.
Drag indicator: maximum or minimum sensor temperature for senso
r 2
Reset: Resets the values