118 Rockwell Automation Publication 520-UM001A-EN-E - February 2013
Chapter 3 Programming and Parameters
Advanced Program Group (continued)
Network Parameter Group
This group contains parameters for the network option card that is installed.
Refer to the network option card’s user manual for more information on the
available parameters.
Modified Parameter Group
This group contains parameters that have their values changed from the factory
default.
When a parameter has its default value changed, it is automatically added to this
group. When a parameter has its value changed back to the factory default, it is
automatically removed from this group.
A570 [P Jump] Related Parameter(s): A567
Sets the frequency amplitude that is added to or subtracted from the commanded frequency. See the diagram at A567 [Max Traverse].
Values Default: 0.00 Hz
Min/Max: 0.00/300.00 Hz
Display: 0.01 Hz
A571 [Sync Time] Related Parameter(s): t062, t063, t065 - t068, A560
Enables the function that holds the drive at the current frequency even if the commanded frequency changes. Used with t062, t063, t065-t068 [DigIn TermBlk xx] 32 “Sync Enable”.
Values Default: 0.0 s
Min/Max: 0.0/3200.0 s
Display: 0.1 s
Hertz
Time
Speed Sync Bit
Change Ref's
[Sync Time]
Drive #1 and #2 Sync Enable Input
[Fiber Status]
New Drive #1 Reference
New Drive #2 Reference
A572 [Speed Ratio]
Stop drive before changing this parameter.
Scales the drive speed command.
Values Default: 1.00
Min/Max: 0.01/99.99
Display: 0.01