Chapter 4
Start-Up After Repair
Be prepared to provide the following information when you contact
support:
x Product Catalog Number
x Product Serial Number
x Firmware Revision Level
Before Applying Power to
the Drive
1. Check for zero volts between DC+ and DC-.
2. Perform forward and reverse biased diode tests, using a digital
multimeter. Refer to Conducting Forward and Reverse Biased Diode
Tests for Major Power Components on page 2-4.
!
ATTENTION: Power must be applied to the drive to perform
the following start-up procedure. Some of the voltages present
are at incoming line potential. To avoid electric shock hazard or
damage to equipment, only qualified service personnel should
perform the following procedure. Thoroughly read and
understand the procedure before beginning. If an event does not
occur while performing this procedure, Do Not Proceed. Remove
Power including user supplied control voltages. User supplied
voltages may exist even when main AC power is not applied to
then drive. Correct the malfunction before continuing.