4-4 Start-Up After Repair
Testing With the Motor
This test allows you to measure several operating parameters and diagnose
problems without connecting the motor to its mechanical load.
1. Verify that input power wiring and grounding is connected.
2. Verify that the motor cables are connected.
3. Verify that the motor load is disconnected.
4. Energize the drive.
5. Start the drive and increase the speed from zero to base speed.
6. Measure drive output current and verify that the value is reflected in:
parameter 308 [Output Current] (700S)
parameter 003 [Output Current] (700H)
7. Stop the drive.