7.7.64 AIN9 Level 1 [ ]
Warning limit level for AIN9
Step: 1
Range: 0 - 10000
Default: 20
7.7.65 AIN9 Level 2 [ ]
Shutdown limit level for AIN9
Step: 1
Range: 0 - 10000
Default: 10
7.7.66 AIN9 Del [s]
Delay for Wrn/Sd AIN9 alarm.
Step: 1s
Range: 0 - 3600s
Default: 10s
NOTE:
Analog input 9 is configurable with basic two levels protection and it is voltage type of input with range
0-10V.
7.7.67 NextServTime [h]
Counting down when engine is running. Service time alarm appears if reaches zero. By setting the
value of 65535h the count down is disabled.
Step: 1h
Range: 0 – 65535h
Default: 10 000
NOTE:
Set the NextServTime = 65535h to disable count down. The setpoint stays constant, but Statistics
value (visible in LiteEdit) displays #### invalid value.
7.7.68 GearBoxRatio [RPM]
There are two new protections related to RPM-BI3 where functions Engine protect: RPMdiff Sd,
RPMdiff Wrn limits depends on setting of GearBoxRatio:
ï‚· Separate RPM-BI3 underspeed Wrn and Sd protection when Engine protect: GearBoxRatio
= 0.0
ï‚· Difference check between RPM and RPM3 with calculation of gear-box ratio, when Engine
protect: GearBoxRatio > 0.0. Protection is active when engine is Ready to load.
Step: 0.1RPM
Range: 0.0 - 5.0RPM

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals