InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
The output opens if there is any reason to stop the engine or in pause between
repeated starts.
HINT
In the case of gas engine, the underspeed protection cannot be blocked by the Sprinkler function.
For gas engines, it is strongly recommended to use the pick-up sensor, as non-zero RPM detection is
required during the start procedure.
7.4.15 FuelSol offset [s]
This setpoint adjusts the Fuel solenoid output activation in relation to Starter output when Fuel
solenoid = GAS. Setpoint values mean that fuel valve is opened after the Starter. FuelSol offset has
effect for both Fuel solenoid = DIESEL or GAS.
Step: 0.1s
Range: 0.0 - 30.0s
Defualt value: 0.5s
Engine starting procedure when Engine params: Fuel solenoid = GAS
BO: Fuel solenoid
BO: Fuel solenoid
RPM > 30
BO: Starter
0 s FuelSol offset
activates
the Fuel solenoid
immediately if RPM > 30.
FuelSol ofset countdown is
started if RPM > 30.
FuelSol offset = 30 s
Fuel solenoid activation
FuelSol offset
up to 30 s
NOTE:
A new feature has been added which prolongs the last cranking attempt by 25% of MaxCrank time
with closed Fuel valve (Fuel Solenoid binary output) in order to ventilate the remaining gas, as is
implemented in IG/IS-NT. This function is valid only when Engine params: Fuel solenoid = GAS
+25%
= MaxCrank time
BO: Fuel solenoid
RPM
BO: Starter
( CrankAttempts - 1) the attempt
The last crank attempt is extended by
25% of MaxCrank time, with Fuel
solenoid closed, to ventilate the gas
from the engine.
Fuel solenoid activation delay can
be set using FuelSol offset .
NOTE:
Is modified functionality of the Ignition binary output. The Ignition binary output will close 1 second
(fixed value) after activation of binary output Fuel solenoid (when Fuel solenoid = GAS setting is
active). Generally, the output closes after reaching value of CrankRPM = 30RPM (fixed value). The
output opens after stopping of the engine or during crank fail pauses among crank attempts.