6.8.1 Engine RPM Idle - Nominal switching
Binary input Nominal/Idle switchs RPM to Engine params: Idle speed when closed (in MAN mode
only). Opened input ramps to Engine params: ECU SpeedAdj. No RPM control is active in engine
Idle state.
6.8.2 Engine RPM two/three levels switching
Continuing example above …. closed BI Speed Sel1, 2, 3 ramps the Engine RPM to the selected
setpoint level. … i.e. switched/ramped to another three levels.
HINT
Necessary condition: Regulator: LAI SpeedReq = OFF and controller MAN mode.
6.8.3 Engine RPM by Up/Down buttons settings
RPM adjusted in examples above can be changed by BI Speed Up / Speed Down when the Engine
params: RetToSpeedAdj = DISABLED.
HINT
Necessary condition: Regulator: LAI SpeedReq = OFF and controller MAN mode.
6.8.4 Engine RPM continuous change (using potentiometer)
Adjust Regulator: LAI SpeedReq = AI1-9 … to corresponding controller or extension module analog
input.
Configure this Analog input - sensor characteristic in RPM or Percentage (expected potentiometer
resistance 2,5kOhm in example below). Engine params: Speed ramp setpoint is active.