94
Engine protect: Uderspeed Sd = ENABLED
RPM <
Engine State
AlarmList
History
ReadyToLoad
Engine protect:
Underspeed
Idle
-
-
Off
Running
Wrn Underspeed
-
On -˃ Off
Engine params:
Starting RPM
Idle
Sd Underspeed
Sd Underspeed
Off
Running
Sd Underspeed
Sd Underspeed
Off
Engine protect: Uderspeed Sd = DISABLED
RPM <
Engine State
AlarmList
History
ReadyToLoad
Engine protect:
Underspeed
Idle
-
-
Off
Running
-
-
On
Engine params:
Starting RPM
Idle
-
-
Off
Running
-
-
On
10 RPM
Idle
Sd Underspeed
Sd Underspeed
On -˃ Off
10 RPM
Running
Wrn Undersped
Sd Underspeed
Sd Underspeed
On -˃ Off
7.7.9 AIN1 Level 1 [Bar]
Warning limit level for ANALOG INPUT 1
Step: 0.1Bar
Range: -10 - +1000Bar
Default: 2.0Bar
7.7.10 AIN1 Level 2 [Bar]
Shutdown limit level for ANALOG INPUT 1
Step: 0.1Bar
Range: -10 - +1000Bar
Default: 1.0Bar
7.7.11 AIN1 Del [s]
Delay for ANALOG INPUT 1
Step: 1s
Range: 0 - 180s
Default: 3s
NOTE:
Analog input 1 is usually determined to Oil Pressure measurement and it is resistive type of input with
range 0-2500Ohm.

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals