13.1.5 List of possible alarms
Events specification
Protection
type
Information on binary
output available (See
list of Binary outputs)
Description
Wrn Oil Press
WRN
YES
Oil pressure is smaller than Wrn Oil
press setpoint.
Sd Oil Press
SD
YES
Oil pressure is smaller than Sd Oil
press setpoint.
Sd NotOilPress
SD
YES
No information about the oil pressure
from the binary oil pressure sensor.
Wrn Engine Temp
WRN
YES
Water temperature is greater than
Wrn Water temp setpoint.
Sd Engine Temp
SD
YES
Water temperature is greater than Sd
Water temp setpoint.
Wrn Fuel Level
WRN
YES
Fuel level is smaller than Wrn Fuel
Level setpoint.
Sd Fuel Level
SD
YES
Fuel level is smaller than Sd Fuel
Level setpoint.
Ubat
WRN
YES
Battery voltage is out of limits given by
Batt overvolt and Batt undervolt
setpoints.
Wrn AIN
WRN
YES
Warning alarm configurable on the
input of the controller
Sd AIN
SD
YES
Shutdown alarm configurable on the
input of the controller.
Wrn AIO
WRN
YES
Warning alarm configurable on the
input of plug-in.
Sd AIO
SD
YES
Shutdown alarm configurable on the
input of plug-in.
Binary input
Configurable
YES
Configurable Warning/Shutdown
alarms on the inputs of InteliDrive Lite.
Battery flat
SD
YES
If the controller switches off during
starting sequence due to bad battery
condition it doesn’t try to start again
and activates this protection.
Start failed
SD
YES
Engine start failed.
RPM meas fail
SD
NO
At least one running condition was
detected (Poil>Starting POil or
energized D+) and do not appear
RPM>Starting RPM.
ParamFail
NONE
NO
Wrong checksum of parameters.
Happens typically after downloading
new firmware or changing of the
parameter. The controller stays in
INIT mode. Check all parameters,
write at least one new parameter.
Overspeed
SD
YES
The protection comes active if the
speed is greater than Overspeed
setpoint.
Underspeed
SD
YES
During starting of the engine when the
RPM reached the value of Starting
RPM setpoint the starter is switched
off and the speed of the engine can
drop under Start RPM again. Then the
Underspeed protection becomes
active. Protection evaluation starts 5
seconds after reaching StartingRPM.
EmergencyStop
SD
NO
If the input Emergency stop is opened

Table of Contents

Other manuals for ComAp InteliDrive Lite