InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
91
Default: 0
7.6.9 Load Integral [%]
This setpoint is giving Load limit integration factor.
Step: 0.1
Range: 0.0% - +100.0%
Default: 0
7.6.10 Load CMP Input [RPM, ECU:Load, CU:AI1, CU:AI2, CU:AI3,
CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8,
CU:AI9, AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4]
This setpoint is for Load limit comparetor with hysteresis analog input selection. Source can be
adjusted from controller RPM pick-up, ECU, analog inputs or from extension module inputs.
Default state: RPM
7.6.11 Load CMP Off
Limit to close LBO LoadSwitch
Step: 1
Range: -10000 - +10000
Default: 95
7.6.12 Load CMP On
Limit to open LBO LoadSwitch
Step: 1
Range: -10000 - +10000
Default: 90
7.7 Engine protect
7.7.1 Eng prot del [s]
During the start of the engine, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protection del time. The time starts after reaching Start RPM.
Step: 1s
Range: 0 - 300s
Default: 5s

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals