InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
9.3.22 Conveyor
Initial condition: Running engine.
Rising edge BI Conveyor activates BO Horn for Engine params: Conveyor horn. And after horn is
over activates the BO Conveyor.
The second rising edge of BI Conveyor opens the BO Conveyor. BO Conveyor is deactivated in case
of Sd protection.
BI Conveyor
BO Conveyor
BO Horn
9.3.23 LoadRequest2
Active input switches the Load limit request to Load limit: LoadRequest2 setpoint.
9.3.24 LoadRegDisable
Active input disables the Load limit PI loop and switches analog output to constant Load limit: Load
bias.
9.3.25 RegRequest2
Active input switches the Regulator limit request to Regulator: Request2 setpoint.
9.3.26 R Reg Disable
Active input disables the Regulator PI loop and switches analog output to constant Regulator: Reg
bias.
9.3.27 Clear DayCons
DayCons is the counter which cumulates the instantanous consumption coming from ECU. It shows
the total consumption since the counter reset. Counte reset happen at the midnight of the controller
clocks. LBI Clear DayCons resets the counter DayCons.
HINT
The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint Engine params:
FuelTankVolume.
9.3.28 Clear TripCons
TripCon is the counter which cumulates the instantanous consumption coming from ECU. It shows the
total consuption since last reset by LBI Clear TripCon. This LBI resets the counter TripCons.
HINT
The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint Engine params:
FuelTankVolume.