7.7.12 AIN2 Level 1 [ ]
Warning limit level for ANALOG INPUT 2
Step: 1ï‚°C
Range: -100 - 10000°C
Default: 80°C
7.7.13 AIN2 Level 2 [ ]
Shutdown limit level for ANALOG INPUT 2
Step: 1ï‚°C
Range: -100 - 10000°C
Default: 90°C
7.7.14 AIN2 Del [s]
Delay for ANALOG INPUT 2 alarm.
Step: 1s
Range: 0 - 180s
Default: 5s
NOTE:
Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type of
input with range 0-2500Ohm.
7.7.15 AIN3 Level 1 [ ]
Warning limit level for ANALOG INPUT 3
Step: 1 %
Range: -100 - +10000%
Default: 20%
7.7.16 AIN3 Level 2 [ ]
Shutdown limit level for ANALOG INPUT 3
Step: 10%
Range: -100 - +10000%
Default: 10%
7.7.17 AIN3 Del [s]
Delay for ANALOG INPUT 3
Step: 1s
Range: 0 - 180s
Default: 10s
NOTE:

Table of Contents