To reduce the data traffic over cellulat network you can set in setpoint group Comms Settings“ the
parameter „AirGate IP“ = 80.95.108.26. This will save significant data amount needed for translation of
Airgate server IP address. In case of changing the server IP address this settings has to be updated or
returned to default „airgate.comap.cz“.
WARNING!
All manipulations with IL-NT-GPRS module has to be done with DC power supply switched off.
Module can be only powered while is plugged into the controller and together with controller!
7.3.16 SMTP UserName [-]
User name or name of e-mail account is used for verification of email sender on SMTP server. If
parameter left empty, no verification is expected. It is working for IB-Lite only.
7.3.17 SMTP UserPass [-]
User password of e-mail account is used for verification of e-mail sender on SMTP server. If
parameter left empty, no verification is expected. It is working for IB-Lite only.
7.3.18 SMTP Server IP [-]
Adjust IP address of SMTP server. It is working for IB-Lite only.
7.3.19 Contr MailBox
E-mail address used as “Sender” of alarm e-mails from IB-Lite.
HINT
If SMTP server requires verification of sender, e-mail address has to be registered to SMTP server
and setpoints “SMTP UserName” and “SMTP UserPass” has to be set to correct values.
7.3.20 Time Zone
List of time zones used for time reference.
7.3.21 DNS IP Address
This is IP address of Domain Name Server.
7.4 Engine params
7.4.1 Starting RPM [RPM]
“Firing” speed when InteliDrive Lite controller stops cranking (starter goes OFF).
Sd Underspeed protection is activated when RPM drops back below the Starting RPM for more than 5
second the engine starting procedure.
HINT
Limit is ignored when Gear teeth = 0 i.e. in engine operation without speed pickup (running state is
indicated from D+ or Starting POil.
Step: 1RPM

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals