Default value: 5s
7.4.6 CrnkFail pause [s]
Pause between crank (engine start) attempts.
Step: 1s
Range: 5 - 60s
Default value: 8s
7.4.7 Crank attempts [-]
Maximum number of crank (engine start) attempts.
Step: 1
Range: 1 - 10
Default value: 3
7.4.8 Idle time [s]
Idle time delay starts when RPM exceeds Start RPM. Start fail is detected when during Idle state RPM
decreases below 2.
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it expires the
IDLE/NOMINAL output closes. Binary output IDLE/NOMINAL opens during Cooling period again.
Note:
Engine can be switched between Idle and Running state by Binary input Nominal/Idle in MAN mode.
Step: 1s
Range: 0 - 600s
Default value: 12s
7.4.9 Idle speed [RPM]
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by
Binary input Nominal/Idle and after Engine ShutDown.
Step: 1RPM
Range: Starting RPM – MinSpeedLimit
Default value: 800RPM

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals