InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf, ©ComAp – August 2015
10 Binary output functions
HINT
Any Binary input can be configured to any InteliDrive Lite controller terminal or changed to different
function by LiteEdit PC tool. There is adjustable delay when any binary input is configured as
protection.
10.1 Binary outputs InteliDrive Lite - default
BO1 Starter
BO2 Fuel solenoid
BO3 Prestart
BO4 Alarm
BO5 Horn
BO6 Not used
BO7 Not used
10.2 Binary outputs – list
Configuration of binary outputs is feasible easily by combo box menu in the configuration window
Modify.
10.2.1 Not used
Output has no function.
10.2.2 Starter
Closed relay energizes the starter of engine.
The relay opens if:
ï‚· the strating speed is reached or
ï‚· maximum time of cranking is exceeded or
ï‚· request to stop comes up
10.2.3 Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
ï‚· Emergency stop comes or
ï‚· cooled engine is stopped or
ï‚· in pause between repeated starts