ID–Lite-2.0 User guide, ©ComAp January 2011 62
ID-Lite-2.0 User guide.pdf
A new feature has been added which prolongs the last cranking attempt by 25% of MaxCrank time
with closed Fuel valve (Fuel Solenoid binary output) in order to ventilate the remaining gas, as is
implemented in IGS-NT. This function is valid only when Engine params: Fuel solenoid = GAS:
Modified functionality of the Ignition binary output
The Ignition binary output will close 1 second (fixed value) after activation of binary output Fuel
solenoid (when Fuel solenoid = GAS setting is active). Generally, the output closes after reaching
value of CrankRPM = (fix) 30 RPM. The output opens after stopping of the engine or during crank fail
pauses among crank attempts.
D+ function [ENABLED, CHRGFAIL, DISABLED]
ENABLED: The D+ terminal is used for both functions “running engine detection and charge fail
detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only.
DISABLED: The D+ terminal is not used.
Hint:
The magnetization current is provided independently on this setpoint value.
The D+ charge fail protection becomes active after Engine params: Idle time reaches zero.
ECU FreqSelect [PRIMARY, SECONDARY, DEFAULT]
Volvo Volvo Aux is selected in ECU configuration:
Primary or secondary engine speed is set by Frequency select bits in VP Status frame.
Scania “Scania S6 Singlespeed is selected in ECU configuration:
Nominal engine speed is chosen by Nominal speed switch 1 and 2 from DLN1 frame when the engine
is running on nominal speed, i.e. binary output Idle/Nominal is active. When the output is not active
(engine is running on Idle speed), the setpoint ECU FreqSelect is not taken into account.
ECU Control [ ENABLED, STARTSTOP, DISABLED ]
The setpoint enables adjustment of the electronic engine control by following settings:
ENABLED there is a full available control of an electronic engine given by the setting of the ECU
unit of the engine, i.e. Start request, Stop request, Speed request are enabled if available
STARTSTOP there is a limited control of an electronic engine reduced to both Start request and
Stop request. The Speed request is blocked.
DISABLED a control of an electronic engine is fully blocked and the ID-Lite can only monitor the
values of an electronic engine.
Default: ENABLED
ECU SpeedAdj [ RPM ]
Enables to adjust engine speed in ECU via CAN bus. Speed request value after the Idle time is over
and no other speed selection is activated.
Speed request in % range is calculated using the setpoints 0%ofSpeedReq and 100%ofSpeedReq.
Step: 1RPM
Range: MinSpeedLim MaxSpeedLim
RetToSpeedAdj [ ENABLED, DISABLED ]
Selection between LBI Speed selection1, ..2, ..3 behavior.

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals