EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite User Manual

ComAp InteliDrive Lite
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
ID–Lite-2.0 User guide, ©ComAp January 2011 63
ID-Lite-2.0 User guide.pdf
DISABLED: Speed request is set by LBI Speed selection1, ..2, ..3 (see corresponding setpoints) by
rising edge (button, no switch) i.e. Speed request stay constant after the input is opened and can be
changed by BI Speed Up and Speed Down.
ENABLED: Speed request goes to ECU SpeedAdj when the LBI Speed selection1, ..2, ..3 is opened.
Speed request can be changed by Binary inputs Speed Up and Speed Down when LBI Speed
selection 1, ..2, ..3 is closed.
MinSpeedLim [RPM]
The setpoint presets the minimum engine speed in the Running operation mode. Also see other
conditions in the chapter below.
Step: 1 RPM
Default: 1200 RPM
Range: Starting RPM MaxSpeedLim
MaxSpeedLim [RPM]
The setpoint presets the maximum engine speed in the Running operation mode. Also see other
conditions in the chapter below.
Step: 1 RPM
Default: 2700 RPM
Range: MinSpeedLim 4000 RPM
BI Speed Sel 1 [RPM]
The setpoint presets the required engine speed during the Speed Sel 1’ binary input is active.
Function depends on RetToSpeedAdj setting.
Step: 1 RPM
Default: 1250 RPM
Range: MinSpeedLim MaxSpeedLim
BI Speed Sel 2 [RPM]
The setpoint presets the required engine speed during the Speed Sel 2’ binary input is active.
Function depends on RetToSpeedAdj setting.
Step: 1 RPM
Default: 1300 RPM
Range: MinSpeedLim MaxSpeedLim
BI Speed Sel 3 [RPM]
The setpoint presets the required engine speed during the Speed Sel 3’ binary input is active.
Function depends on RetToSpeedAdj setting.
Step: 1 RPM
Default: 1450 RPM
Range: MinSpeedLim MaxSpeedLim
Hint:
When none of the binary inputs: Speed Sel 1’, Speed Sel 2’ and Speed Sel 3’, Speed Up’ and
Speed Down’ has not been configured then engine speed is given by theEngine params: ECU
SpeedAdj setpoint.
BI Speed Ramp [ RPM/s ]
Any Speed request change is done via this Ramp function. The Ramp via Binary SpeedUp and
SpeedDown inputs is dual rate se below.

Table of Contents

Other manuals for ComAp InteliDrive Lite