ID–Lite-2.0 User guide, ©ComAp – January 2011 69
ID-Lite-2.0 User guide.pdf
Horn timeout [s]
Max time limit of horn sounding. Set to zero if you want to leave the output HORN open. Horn timeout
starts again from the beginning if a new alarm appears before previous Horn timeout has elapsed.
Step: 1s
Range: 0 – 600 s
Overspeed [%]
Limit for engine Sd overspeed protection.
Step: 1% of nominal RPM
Range: 50 – 150%
Underspeed [%]
The limit for Warning Underspeed protection. Active protection is indicated as “Wrn underspeed” in
Alarm list. Under speed Warning protection is inactive 5 second after RPM is over Engine params:
Starting RPM and during the Idle time.
The “Ready to load” output is deactivated when Wrn underspeed protection is active and needs the
Fault reset for activation after RPM is over Underspeed limit.
Step: 1% of nominal RPM
Range: Starting RPM – 100%
Engine params: Starting RPM
Engine protect: Underspeed
5s
Engineparams: Idle time
Engineprotect: Eng prot del
Warning level
Shut-down level
R
P
M
W
r
n
U
n
d
e
r
s
p
e
e
d
S
d
U
n
d
e
r
s
p
e
e
d
UnderspeedSd [ ENABLED / DISABLED ]
The UnderspeedSd parameter specifies if underspeed shutdown protection limit is given by Starting
RPM parameter (ENABLED) or set to fix level = 10RPM (DISABLED).
AnlInp1 level1 [Bar]
Warning limit level for ANALOG INPUT 1
Step: 0,1 Bar
Range: -10 – 1000 Bar
AnlInp1 level2 [Bar]
Shutdown limit level for ANALOG INPUT 1
Step: 0,1 Bar
Range: -10 – 1000 Bar
AnlInp1 del [s]
Delay for ANALOG INPUT 1
Step: 1 s