ID–Lite-2.0 User guide, ©ComAp January 2011 70
ID-Lite-2.0 User guide.pdf
Range: 0 180 s
AnlInp2 level1 [ ]
Warning limit level for ANALOG INPUT 2
Step: 1 °C
Range: -100 10000
AnlInp2 level2 [ ]
Shutdown limit level for ANALOG INPUT 2
Step: 1 °C
Range: -100 10000
AnlInp2 del [s]
Delay for ANALOG INPUT 2 alarm.
Step: 1 s
Range: 0 180 s
AnlInp3 level1 [ ]
Warning limit level for ANALOG INPUT 3
Step: 1 %
Range: -100 10000
AnlInp3 level2 [ ]
Shutdown limit level for ANALOG INPUT 3
Step: 1 %
Range: -100 10000
AnlInp3 del [s]
Delay for ANALOG INPUT 3
Step: 1 s
Range: 0 180 s
Batt overvolt [V]
High battery voltage Warning limit.
Step: 0,1 V
Range: 8(Batt undervolt ) 40 V
Batt undervolt [V]
Low battery voltage Warning limit.
Step: 0,1 V
Range: 8V 40 (Batt overvolt)
Batt volt del [s]
Delay for low and high battery voltage alarm.
Step: 1s
Range: 0 600 s
NextServTime [h]
Counting down when engine running. Service time alarm appears if reaches zero.
Step: 1h
Range: 0 65535h
GearBoxRatio [ - ]
There are two new protections related to RPM-BI3 where function of Engine protect: RPMdiff Sd,
RPMdiff Wrn limits depends on setting of GearBoxRatio:

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals