5.5.1 Operating Modes
Selecting the operating mode is done with the Left and the Right buttons on the front panel or by
changing the Controller Mode (page 216) setpoint (from the front panel or remotely).
Note: If this setpoint is configured as password-protected, the correct password must be entered prior to
attempting to change the mode.
Note: The mode cannot be changed if Access Lock input is active.
The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
Remote OFF (page 458)
Remote TEST (page 460)