InteliLite4 AMF20 Global Guide
482
Related FW 1.3.0 Related applications AMF,MRS
Comm object 42
Description
The output is intended for control of close coil of generator circuit breaker. The output gives at least 5
second pulse in the moment the breaker has to be closed.
Image 8.38 GCB ON Coil close command
GCB ON Coil
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 44
Description
The output is intended for control of undervoltage coil of generator circuit breaker. The output is active the
whole time when the generator is running. The output is deactivated for at least 5 seconds in the moment
the breaker has to be switched off.
GCB UV Coil