237
Minimal Stabilization Time
Setpoint group Engine settings Related FW 1.3.0
Range [units] 1 .. Maximal Stabilization Time (page 238) [s]
Default value 2 s Alternative config NO
Step 1 s
Comm object 8259 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
When the Gen-set has been started and the idle timer has elapsed, the controller will wait for a period
adjusted by this setpoint before closing GCB, even if the generator voltage and frequency are already in
limits.
Note: When starting the engine, setpoint should be set >300s.
Image 8.5 Minimal Stabilization Time
6 back to List of setpoints