InteliLite4 AMF20 Global Guide
226
Maximum Cranking Time
Setpoint group Engine settings Related FW 1.3.0
Range [units] 1 .. 255 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8256 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
Maximum time limit of cranking time.
6 back to List of setpoints
Cranking Fail Pause
Setpoint group Engine settings Related FW 1.3.0
Range [units] 5 .. 60 [s]
DefaultFixed
value
8 s Alternative config NO
Step 1 s
Comm object 8257 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
Pause between Cranking Attempts (page 225). PRESTART (PAGE 496) output is active in this pause until
Cranking Fail Pause elapses.
6 back to List of setpoints